Technical data
11/15
Building Technologies REV200…RF room temperature controller CE1N2214en
HVAC Products 28.08.2008
a) Switch off power
b) Mark location where REV-R… is currently fixed
c) If necessary loosen wiring
d) Mount receiver at location marked before, wire completely and close housing
e) Switch on mains power
• In the event of a power failure at the REV-R…, the relay will be deenergized.
• If in normal operation REV-R… does receive for more than 25 minutes a very weak
or no control telegram from REV200…, LED_1 starts to flash in red.
If control telegram is still understood correctly, receiver continues with normal
operation. If control telegram is not understood anymore, relay remains in last
position being switched to before.
As soon as REV-R… does receive any correct control telegram from REV200…
again, receiver continuous with normal operation
• In case of error, REV-R… switches off relay approximately 60 minutes after
reception of last correct control telegram. The controlled device is also switched off
and LED_1 flashes in red.
As soon as REV-R… does receive any correct control telegram from REV200…
again, receiver continuous with normal operation
7. Finishing
mounting of
REV-R…
Notes