Technical data
10/15
Building Technologies REV200…RF room temperature controller CE1N2214en
HVAC Products 28.08.2008
LED_1 flashes green: We distinguish between three signal strengths:
Very good (flashes 3x), Good (flashes 2x) and
Satisfactory (flashes 1x).
As soon as LED_1 flashes in green, link between
REV200…and REV-R… is basically ok.
g) Move REV-R… within an area of approximately 1 square meter to find location of
best RF reception. Always observe LEDs from a distance of 2…3 meters. To get a
durable link, we recommend to site REV-R… at a location where signal strength is
at least “Good”.
Reption of control telegram
6. Explanations
to LEDs
LED_1 lights always
in red
LED_1 flashes in red
LED_1 flashes
3 times in green
LED_1 flashes
2 times in green
LED_1 flashes
1 time in green
LED_2 is always off
LED_2 is always on
LED_2 flashes always
LED_2 flashes briefly
Red on
Red off
No REV200… linked
Red on
Red off
Signal strength too weak
Green on
Green off
Si
g
nal stren
g
th: Ver
y
g
ood
1 2 3
1 2 3
Starting
sequence
Starting
sequence
Green on
Green off
Si
g
nal stren
g
th: Good
1 2
1 2
Starting
sequence
Starting
sequence
Starting
sequence
Green on
Green off
Si
g
nal stren
g
th: Satisfactor
y
1
1
Starting
sequence
Starting
sequence
1
Starting
sequence
Orange on
Orange off
Controlled device OFF
Orange on
Orange off
Controlled device ON
Orange on
Orange off
Learning mode active