User Manual

Controlled device ON
LED_2 is always on
Orange on
Orange off
Learning mode active
LED_2 flashes
continuously
Orange on
Orange off
Repetition of control telegram
LED_2 flashes briefly
a) Switch off power
7. Finishing
mounting of
REA-R.03/1
b) Mark location where REA-R.03/1 is currently fixed
c) If necessary loosen wiring
d) Mount receiver at location marked before, wire completely and close housing
e) Switch on mains power
Notes
If, during normal operation, the REA-R.03/1 receives either a very weak control
telegram from REA23.03RF or no control telegram for longer than 25 minutes,
LED_1 starts to flash in red.
If the control telegram is still understood correctly, the receiver continues with nor-
mal operation. If the control telegram is no longer understandable, the relay re-
mains in the last switching position.
As soon as the REA-R.03/1 does receive a correct control telegram from the
REA23.03RF again, the receiver continues with normal operation
In case of error, REA-R.03/1 switches off the relay approximately 60 minutes after
receipt of the last correct control telegram. The controlled device is also switched
off and LED_1 flashes in red.
As soon as the REA-R.03/1 does receive a correct control telegram from
REA23.03RF again, the receiver continues with normal operation
In the event of a power failure at the REA-R.03/1, the relay is de-energized.
12/16
Building Technologies Room temperature controller REA23.03RF CE1N2218en
HVAC Products 17.04.2007