Submittal Sheet

NEW!
THERMOSTATS & CONTROLLERS
1354
NEW!
THERMOSTATS & CONTROLLERS
21
EASY RETURNS, LET KELE DO THE LEGWORK
kele.com877-826-9037 USA
September 2016
Jumper
RH-RC
If dual transformers are used, remove jumper RH-RC and
connect C to the common on the cooling traansformer only.
OUT
3
C3 Y1 Y2 O/BGRC RH CW1W2
OUT
1
OUT
2
IN1INC IN2IN3 INCIN4
Configurable
Output 3
Compressor
1
Compressor
2
Heating
Stage 2
Configurable
Output 2
See Note 1
Heating
Stage 1
Configurable
Output 1
(Stage 3 Cooling
if 3H/3C)
Fan
Input 1 Input 2 Input 3 Input 4
24 VAC
NOTE 1:
O/B Terminal Function in 3 Stage
Conventional Systems
System
Configuration
0H/3C
O/B Terminal Function
Stage 3 Cooling
1H/3C Stage 3 Cooling
2H/3C Stage 3 Cooling
3H/0C Stage 3 Heating
3H/1C Stage 3 Heating
3H/2C Stage 3 Heating
3H/3C
O/B: Stage 3 Heating
(OUT1: Stage 3 Cooling)
System
Transformer
(Note 2)
Jumper
RH-RC
If dual transformers are used, remove jumper RH-RC and
connect C to the common on the cooling traansformer only.
Jumper
RC-C3
Installed
Aux Output 3 Jumper RC-C3 Placement
OUT
3
Configurable
Output 3
(30V max.)
To XF
Common
Jumper
RC-C3
Removed
OUT
3
Configurable
Output 3
(30V max.)
C3
OUT
3
C3 Y1 Y2 O/BGRC RH CW1W2
OUT
1
OUT
2
IN1INC IN2IN3 INCIN4
Configurable
Output 3
Compressor
1
Compressor
2
Aux Heat 2
Configurable
Output 2
Reversing
Valve
Aux Heat 1
Fan
Input 1 Input 2 Input 3 Input 4
24 VAC
Configurable
Output 1
System
Transformer
(Note 2)
Heat Pump
WIRING
Conventional System
Note 2: 24VAC Class 2 Control Transformer: Maximum transformer load 80% (4A rating maximum load 3.2A).
Install with mounting feet to grounded equipment chassis. Connect common to grounded equipment chassis at transformer
Wiring Schematic, Heat Pump
ORDERING INFORMATION
MODEL DESCRIPTION
RDY2000 3H/3C & HP Commercial Programable Room Thermostat with Remote Sensor Inputs
RDY2000BN 3H/3C & HP Commercial Programable Room Thermostat, BACnet with Remote Sensor Inputs
ACCESSORIES
QAA2330.EWNN Remote wall mounted sensor - temperature only
QAC2030 Outdoor air temperature sensor
QAD2030 Surface mount pipe temperature sensor
QAM2030.010 Duct mounted temperature sensor
QFA33SS.EWNN Remote wall mounted temperature & humidity sensor
QFM2160U Duct mounted temperature & humidity sensor
QPA2000 Wall mounted CO2 sensor
QPA2062 Wall mounted temperature + humidity + CO2 sensor
QPM2162 Duct mounted temperature + humidity + CO2 sensor
BACNET OR CONVENTIONAL COMMERCIAL ROOM THERMOSTAT
RDY2000, RDY2000BN