Install Instructions

Document No. 129-905
Installation Instructions
March 26, 2015
Siemens Industry, Inc.
Page 9 of 18
Table 4. 200 Series Parameters.
Parameter Definition Display Value Range Default Extended Definition Notes
P201
Heat Temp
Limit
HEAT LIMIT
45°F to 95°F
(7.0°C to 35.0°C)
95°F
(35.0°C)
Sets maximum allowable heating set
point.
Does not appear if P103 = 0.
P202
Cool Temp
Limit
COOL LIMIT
50°F to 95°F
(10.0°C to
35.0°C)
50°F
(10.0°C)
Sets minimum allowable cooling set
point.
Does not appear if P102 = 0.
P203
Temperature
Display
Offset
TMP OFFSET
-5°F to 5°F
(-3.0°C to
3. 0°C)
0°F
(0°C)
Enables adjustment of control temp and display temperature in 1
degree increments. Applies only to onboard temp sensor. Indoor temp
only.
P204
Override
Time Limit
HRS OVR RD 0 to 96 hours ---
Number of hours that scheduled
setpoint can be manually overridden.
0 = No override allowed
--- = Unlimited
This parameter will not
appear if P107 = 0.
P205
Override
Temp Limit
TMP OVR RD
1°F to 10°F
(0.5°C to 4.0°C)
---
Number of degrees that are allowed
above or below scheduled setpoint.
--- = Unlimited
This parameter will not
appear if P107 or P204 = 0.
P206
Heat Pump
Compressor
Lock Out
HP COMP LO
OFF
15°F (-9.0°C)
20°F (-6.C)
25°F (-3.0°C)
30°F (-1.0°C)
35°F (1.0°C)
40°F (4.0°C)
45°F (7.0°C)
OFF
Heat pump compressor will not
operate below this outdoor temp --
forcing unit to auxiliary heat. An
outdoor temperature sensor is
required.
NOTE: If P206 ≠ OFF, set P508 = 1°F
(0.5°C).
This parameter only appears
for the following conditions:
- P101 = HP.
- P104 > 0.
- P105 = YES
- P301, P305, P309,
or P313=5
- P206 < P207.
P207
Heat Pump
Auxiliary
Heat Lockout
HP AUX LO
OFF
40°F (4.0°C)
45°F (7.0°C)
50°F (10.0°C)
55°F (13.0°C)
60°F (16.0°C)
OFF
Heat pump auxiliary heat will not
operate above this outdoor temp. An
outdoor temperature sensor is
required.
This parameter only appears
for the following conditions:
- P101 = HP.
- P104 > 0.
- P301, P305, P309,
or P313 = 5
- P207 > P206.
P208
Service UV
Lamp
UV LAMP 0 to 365 days 0
Number of calendar days until
SERVICE UV LAMP message
displays.
0 = function disabled.
P209
Service
Humidifier
HMDFR
SRVC
0 to 365 days 0
Number of calendar days until
SERVICE HUMIDIFIER message
displays.
0 = function disabled.
P210
Service Air
Filter
FLTR SRVC 0 to 365 days 0
Number of calendar days until
SERVICE AIR FILTER message
displays.
0 = function disabled.
P211
Keypad
Lockout
KEY LOCK
0 = NONE
1 = PARTIAL
2 = FULL
0
0 = No Lockout
1 = Partial Lockout (only temp setpoint
can be adjusted)
2 = Total Lockout
Keypad lock icon [ ]
displays if P211 > 0.
P212 Clock Format CLOCK
12
24
12
12 = 12-hour format
24 = 24-hour format
P213 Backlight LIGHT 0 to 99 seconds 15
Number of seconds that backlight
stays on after screen is touched.
0 = Always off.