Install Instructions
Document No. 129-905
Installation Instructions
March 26, 2015
Page 10 of 18 Siemens Industry, Inc.
Table 5. 300 Series Parameters.
Parameter Definition Display
Value
Range
Default Extended Definition Notes
P301
Configurable
Input 1 (IN1)
INPUT 1
0
1
2
3
4
5
6
7
8
9
0
0 = Not Used
1 = Indoor Temperature (Remote)
2 = Indoor Temperature (Average)
3 = Supply Temp
4 = Return Temp
5 = Outdoor Temp
6 = Humidity (0-10V)
7 = CO2 (0-10V)
8 = Occupancy (DI)
9 = Fault
- Selections for inputs 1-4
cannot be duplicated.
- If set to 9 (fault), a DI here
causes SERVICE
REQUIRED segment to
activate.
- See Table 14
for a list of
optional sensors
approved for use with the
RDY2000.
P302
Temperature
Input 1 Type
TMP IN 1
0
1
0
0 = Type 2 Thermistor
1 = 0-10V
Only appears if
P301=1/2/3/4/5.
P303
Temperature
Input 1 Low
TMP 1 LO
-58°F to
120°F **
(-50.0°C to
50.0°C)
0°F
(-18.0°C)
Calibrates thermostat to low end of temp
sensor signal (for example, 0V = -40°F
[4.4°C])
- Only appears if P302=1
** P303<P304.
P304
Temperature
Input 1 High
TMP 1 HI
P303 value
** to 250°F
(120.0°C)
120°F
(50.0°C)
Calibrates thermostat to high end of
temp sensor signal at 10 volts (for
example, 10V = 250°F [120.0°C])
- Only appears if P302=1.
** P304>303.
P305
Configurable
Input 2 (IN2)
INPUT 2
0
1
2
3
4
5
6
7
8
9
0
0 = Not Used
1 = Indoor Temperature (Remote)
2 = Indoor Temperature (Average)
3 = Supply Temp
4 = Return Temp
5 = Outdoor Temp
6 = Humidity (0-10V)
7 = CO2 (0-10V)
8 = Occupancy (DI)
9 = Fault
- Selections for Inputs 1-4
cannot be duplicated.
- If set to 9 (fault), a DI
causes SERVICE
REQUIRED segment to
activate
- See Table 14
for a list of
optional sensors
approved for use with the
RDY2000.
P306
Temperature
Input 2 Type
TMP IN 2
0
1
0
0 = Type 2 Thermistor
1 = 0 to 10V
Only appears if P305 =
1/2/3/4/5.
P307
Temperature
Input 2 Low
TMP 2 LO
-58°F to
120°F **
(-50.0°C to
50.0°C)
0°F
(-18.0°C)
Calibrates thermostat to low end of temp
sensor signal (for example, 0V = -40°F)
- Only appears if P306 = 1.
** P307 < P308
P308
Temperature
Input 2 High
TMP 2 HI
P307 value
** to 250°F
(120.0°C)
120°F
(50.0°C)
Calibrates thermostat to high end of
temp sensor signal at 10 volts (for
example, 10V = 250°F).
- Only appears if P306 = 1.
** P308 > P307.
P309
Configurable
Input 3 (IN3)
INPUT 3
0
1
2
3
4
5
6
7
8
9
0
0 = Not Used
1 = Indoor Temperature (Remote)
2 = Indoor Temperature (Average)
3 = Supply Temp
4 = Return Temp
5 = Outdoor Temp
6 = Humidity (0 to 10V)
7 = CO2 (0 to 10V)
8 = Occupancy (DI)
9 = Fault
- Selections for Inputs 1-4
cannot be duplicated.
- If set to 9 (fault), a DI
here causes SERVICE
REQUIRED segment to
activate.
- See Table 14
for a list of
optional sensors
approved for use with the
RDY2000.
P310
Temperature
Input 3 Type
TMP IN 3
0
1
0
0 = Type 2 Thermistor
1 = 0-10V
Only appears if P309 =
1/2/3/4/5.