User Manual

Application 14901 Point Database
38
Siemens Industry, Inc.
Application Note, App 14901
140-1230
2020-02-11
Object Type
Object
Instance
(Point
Number)
Object Name
(Descriptor)
Read (R)/
Write (W)
Present
Value
Write Values
Read (R)/
Write (W)
Out of Service
MultistateValue
15
StgDifCl
W
(1) 1F/0.5C; (2) 2F/1C; (3) 3F/1.5C;
(4) 4F/2C; (5) 5F/2.5C; (6) 6F/3C;
(7) 7F/3.5C; (8) 8F/4C; (9) 9F/4.5C;
(10) 10F/5C
R
MultistateValue
16
CoolingDB
W
(1) 1F/0.5C; (2) 2F/1C; (3) 3F/1.5C;
(4) 4F/2C; (5) 5F/2.5C
R
MultistateValue
17
StgDifHt
W
(1) 1F/0.5C; (2) 2F/1C; (3) 3F/1.5C;
(4) 4F/2C; (5) 5F/2.5C
R
MultistateValue
18
HeatingDB
W
(1) 1F/0.5C; (2) 2F/1C; (3) 3F/1.5C;
(4) 4F/2C; (5) 5F/2.5C
R
MultistateValue
19
BaudRate
W
(1) 9600; (2) 19200; (3) 38400;
(4) 57600; (5) 76800; (6) 115200;
(7) Auto
R
MultistateValue
20
SchEditMode
R
N/A
R
MultistateValue
21
HpCompLock
W
(1) Off; (2) 15F/-9C; (3) 20F/-7C;
(4) 25F/-4C; (5) 30F/1C;
(6) 35F/2C; (7) 40F/4C; (8) 45F/7C
R
MultistateValue
22
HpAuxLock
W
(1) Off; (2) 40F/4C; (3) 45F/7C;
(4) 50F/10C; (5) 55F/13C; (6) 60F/16C
R
MultistateValue
3
23
HeatCoolMode
W
(1) COOLING; (2) HEATING;
(3) AUTO; (4) Off
W
MultistateValue
3
24
SchedMode
W
(1) Comfort; (2) Economy;
(3) Protect
W
MultistateValue
25
ModeEff
R
N/A
W
MultistateValue
26
RM OP MODE
R
N/A
W
Schedule
4
0
WeeklySchedule_1
R
N/A
W
1) This point has a resolution of 0.10.
2) This point has a writable polarity property.
3) This point has a relinquish default that can be written.
4) See the Scheduling section for more information on configuring a schedule.