User Manual

Application 14901 Point Database
36
Siemens Industry, Inc.
Application Note, App 14901
140-1230
2020-02-11
Object Type
Object
Instance
(Point
Number)
Object Name
(Descriptor)
Read (R)/
Write (W)
Present
Value
Write Values
Read (R)/
Write (W)
Out of Service
BinaryValue
1
RevValveMode
W
(0) Cooling; (1) Heating
R
BinaryValue
2
SemiContFan
W
(0) No; (1) Yes
R
BinaryValue
3
FanOpr
W
(0) Gas; (1) Electric
R
BinaryValue
4
Eco_MstEn
W
(0) Disabled; (1) Enabled
R
BinaryValue
5
Eco_MstCtrl
W
(0) Disabled; (1) Enabled
R
BinaryValue
6
HumidityIndp
W
(0) No; (1) Yes
R
BinaryValue
7
Changeover
W
(0) Manual; (1) Auto
R
BinaryValue
8
ClockFormat
W
(0) 12-hour; (1) 24-hour
R
BinaryValue
9
AckService
W
(0) NoAction; (1) Clear
R
BinaryValue
10
Units
W
(0) Deg F; (1) Deg C
R
BinaryValue
11
DST
W
(0) Disabled; (1) Enabled
R
BinaryValue
12
SpDispMode
W
(0) Absolute; (1) Relative
R
BinaryValue
13
OcupyInput
R
N/A
W
BinaryValue
14
HmdyOn
R
N/A
W
BinaryValue
15
DeHmdyOn
R
N/A
W
BinaryValue
16
OcupyStatus
R
N/A
W
BinaryValue
17
DCV
R
N/A
W
BinaryValue
18
ExtFault
R
N/A
W
BinaryValue
19
EcomzrOn
R
N/A
W
BinaryValue
20
SrvcUvLamp
R
N/A
W
BinaryValue
21
SrvcHmdy
R
N/A
W
BinaryValue
22
SrvcFilter
R
N/A
W
BinaryValue
23
HpCompLockOn
R
N/A
W
BinaryValue
24
HpAuxLockOn
R
N/A
W
BinaryValue
25
OverCurrent
R
N/A
W
BinaryValue
26
SchOcupy
R
N/A
W
BinaryValue
27
HmiOcupy
R
N/A
W
BinaryValue
28
VntlationEff
R
N/A
W
BinaryValue
29
PrePurgeEn
R
N/A
W