User Manual

Application 14901 Point Database
35
Siemens Industry, Inc.
Application Note, App 14901
140-1230
2020-02-11
Object Type
Object
Instance
(Point
Number)
Object Name
(Descriptor)
Read (R)/
Write (W)
Present
Value
Write Values
Read (R)/
Write (W)
Out of Service
AnalogValue
26
TmpIn4Low
W
-58 250; -50 120
R
AnalogValue
27
TmpIn4High
W
-58 250; -50 120
R
AnalogValue
28
InstallPW
W
0000 4999
R
AnalogValue
29
ExpertPW
W
5000 9999
R
AnalogValue
30
HeatingSp
R
N/A
R
AnalogValue
31
CoolingSp
R
N/A
R
AnalogValue
32
ComfortClgSP
W
50 95; 5 3
R
AnalogValue
33
ComfortHtgSP
W
45 95; 7 - 40
R
AnalogValue
34
EconClgSP
W
45 - 104; 8 40
R
AnalogValue
35
EconHtgSP
W
40 104; 5 40
R
AnalogValue
36
CoolStg
W
0 2 stages
R
AnalogValue
37
PreOcpyPrg
W
0 3 hours
R
AnalogValue
38
MS/TP MAC
W
0 255
R
AnalogValue
39
ProtClgSP
W
45 - 104; 8 40
R
AnalogValue
40
ProtHtgSP
W
40 104; 5 40
R
AnalogValue
41
UnitNumber
W
0 999
R
AnalogValue
42
HEAT LIMIT
W
45 95; 7 35
R
AnalogValue
43
COOL LIMIT
W
50 95; 10 35
R
AnalogValue
44
APPLICATION
R
N/A
R
AnalogValue
45
IndoorTmpRmt
R
N/A
W
AnalogValue
46
CO2
R
N/A
W
AnalogValue
47
SupplyTmp
R
N/A
W
AnalogValue
48
ReturnTmp
R
N/A
W
AnalogValue
49
OutDoorTmp
R
N/A
W
AnalogValue
50
IndoorTmpAvg
R
N/A
W
AnalogValue
51
Humidity
R
N/A
W
AnalogValue
52
IndoorTmpEff
R
N/A
W
AnalogValue
53
FanRunTime
R
N/A
W
BinaryValue
3
0
FanMode
W
(0) Auto; (1) Manual
W