User Manual
Application 14901 Point Database
34
Siemens Industry, Inc.
Application Note, App 14901
140-1230
2020-02-11
Object Type
Object
Instance
(Point
Number)
Object Name
(Descriptor)
Read (R)/
Write (W)
Present
Value
Write Values
Read (R)/
Write (W)
Out of Service
BinaryOutput
2
,
3
6
AuxOutput1
W
(0) RelayOff; (1) Relay On
W
BinaryOutput
2
,
3
7
AuxOutput2
W
(0) RelayOff; (1) Relay On
W
BinaryOutput
2
,
3
8
AuxOutput3
W
(0) RelayOff; (1) Relay On
W
AnalogValue
0
HmdySp
W
10 – 90%
R
AnalogValue
1
DeHmdySp
W
10 – 90%
R
AnalogValue
2
CO2Setpoint
W
500 – 2000 ppm
R
AnalogValue
3
ChgOvrDB
W
3 – 9℉; 2 – 5℃
R
AnalogValue
4
TmpOffset
W
-5 – 5℉; -3 – 3℃
R
AnalogValue
5
ChgOvrDly
W
1 – 60 min
R
AnalogValue
6
MinOnTimeHt
W
1 – 10 minutes
R
AnalogValue
7
MinOffTimeHt
W
1 – 10 minutes
R
AnalogValue
8
MinOffTimeCl
W
1 – 10 minutes
R
AnalogValue
9
MinOnTimeCl
W
1 – 10 minutes
R
AnalogValue
10
OccMinRun
W
3 – 60 minutes
R
AnalogValue
11
StgDlyHt
W
1 – 10 minutes
R
AnalogValue
12
StgDlyCl
W
1 – 10 minutes
R
AnalogValue
13
HeatStg
W
0 – 2 stages
R
AnalogValue
14
AuxHeatStg
W
0 – 2 stages
R
AnalogValue
15
HrsOvrRide
W
0 – 96 hours
R
AnalogValue
16
UvLampSrvc
W
0 – 365 days
R
AnalogValue
17
HmdfrSrvc
W
0 – 365 days
R
AnalogValue
18
FilterSrvc
W
0 – 365 days
R
AnalogValue
19
BackLight
W
0 – 99 seconds
R
AnalogValue
20
TmpIn1Low
W
-58 – 250℉; -50 – 120℃
R
AnalogValue
21
TmpIn1High
W
-58 – 250℉; -50 – 120℃
R
AnalogValue
22
TmpIn2Low
W
-58 – 250℉; -50 – 120℃
R
AnalogValue
23
TmpIn2High
W
-58 – 250℉; -50 – 120℃
R
AnalogValue
24
TmpIn3Low
W
-58 – 25℉; -50 – 120℃
R
AnalogValue
25
TmpIn3High
W
-58 – 25 ℉; -50 – 120℃
R