User Manual
Application 14901 Point Database
33
Siemens Industry, Inc.
Application Note, App 14901
140-1230
2020-02-11
1) Object Types are: Analog Input (AI), Analog Value (AV), Binary Input (BI), Binary
Value (BV), Multistate Value (MV), and Binary Output (BO).
2) A single value in a column means that the value is the same in English units and in
SI units.
3) This object has an internal algorithm commanding at Priority 16. To issue a
command to the object, use a higher priority.
NOTES:
1. The RDY2000BN commands its points at Priority 16.
2. To change between Heat Pump and Conventional Applications, write to the Point
System Type rather than the Application Point.
Table 5: Points that Can be Read and Written.
Object Type
Object
Instance
(Point
Number)
Object Name
(Descriptor)
Read (R)/
Write (W)
Present
Value
Write Values
Read (R)/
Write (W)
Out of Service
AnalogInput
1
0
UI1.NTC10K
R
N/A
W
AnalogInput
1
1
UI1.10V
R
N/A
W
AnalogInput
1
2
UI2.NTC10K
R
N/A
W
AnalogInput
1
3
UI2.10V
R
N/A
W
AnalogInput
1
4
UI3.NTC10K
R
N/A
W
AnalogInput
1
5
UI3.10V
R
N/A
W
AnalogInput
1
6
UI4.NTC10K
R
N/A
W
AnalogInput
1
7
UI4.10V
R
N/A
W
AnalogInput
1
8
OnbrdTmp
R
N/A
W
AnalogInput
1
9
OnbrdRH
R
N/A
W
BinaryInput
2
0
DI1
R
N/A
W
BinaryInput
2
1
DI2
R
N/A
W
BinaryInput
2
2
DI3
R
N/A
W
BinaryInput
2
3
DI4
R
N/A
W
BinaryOutput
2
,
3
0
O/B
W
(0) RelayOff; (1) Relay On
W
BinaryOutput
2
,
3
1
FanCmd
W
(0) RelayOff; (1) Relay On
W
BinaryOutput
2
,
3
2
Y1
W
(0) RelayOff; (1) Relay On
W
BinaryOutput
2
,
3
3
Y2
W
(0) RelayOff; (1) Relay On
W
BinaryOutput
2
,
3
4
W1
W
(0) RelayOff; (1) Relay On
W
BinaryOutput
2
,
3
5
W2
W
(0) RelayOff; (1) Relay On
W