Auxiliary Sequences
The RDY2000BN primary sequences are designed to control single and multi-stage
heating/cooling systems to maintain a user-defined temperature setpoint.
The following auxiliary sequences are available to optimize occupant comfort and
system efficiency:
Humidification
If one of the configurable digital outputs is configured for a humidification function, the
corresponding relay will close and enable a 24 Vac output signal to be transmitted to
the humidification device. Humidification and dehumidification relays, if configured as
such, cannot be energized simultaneously.
The humidification relay (monitored through HmdyOn) will be energized when
measured humidity drops approximately 4% below setpoint and will be de-
energized when measured humidity reaches the setpoint. Deadbands and proof
timers are enforced to prevent short cycling. Thermostat defaults to control
humidification in Heating mode only.
You must enter a humidity setpoint (HmdySp). The valid range is 10 to 90%; the
default value is 25%. If the humidity drops to 4% below the setpoint (HmdySp), a
30-second proof timer engages. If the humidity is still 4% below the setpoint after
the proof timer times out, the humidification relay energizes.