Sequence of Operation
Fan Operation
17
Siemens Industry, Inc.
Application Note, App 14901
140-1230
2020-02-11
Figure 5: Compressor Staging with Ambient Lockout Activated.
Fan Operation
AUTO Mode The fan relay is energized upon a call for heating or cooling per the
operating sequence. When there is no demand for heating or cooling (none of
heating/cooling stages are activated) the fan relay is de-energized.
The fan will turn ON when one of the following conditions has been met:
In Heating mode, when the compressor or stage of electric heat is ON.
In Cooling mode, 15 seconds before the first stage of cooling is energized.
The fan will turn OFF only after the following condition has been met:
The compressor and stages of electric heat have been OFF for at least 30
seconds.
ON Mode The fan relay is energized regardless of whether or not there is a call for
heating or cooling, unless the unit is set to Unit Off.
Fan Opr - Using Parameter P105 (HTG FAN), the fan relay can be set to be energized
or not energized upon call for heat. This parameter does not apply to compressors; the
fan relay should be energized upon a call for heat on Y1/Y2 regardless of the setting of
the parameter.