BACnet MS/TP MAC Address
The following few screens depicts how
to configure the BACnet parameters for
proper communications.
This configures the MAC address of the
RDY2000BN on any particular MS/TP
network. While the normal range is 0 –
255, many BMS, such as the Siemens
branded ones, require the unit to be
configured as a Master node. To be a
master node, it needs to be set to
between 1 and 127.