User Manual
Application 14900 Point Database
35
Siemens Industry, Inc.
Application Note, App 14900
140-1231
2020-02-11
Object Type
Object
Instance
(Point
Number)
Object Name
(Descriptor)
Read (R)/
Write (W)
Present
Value
Write Values
Read (R)/
Write (W)
Out of Service
BinaryValue
25
OverCurrent
R
N/A
W
BinaryValue
26
SchOcupy
R
N/A
W
BinaryValue
27
HmiOcupy
R
N/A
W
BinaryValue
28
VntlationEff
R
N/A
W
BinaryValue
29
PrePurgeEn
R
N/A
W
MultistateValue
0
Periods
R
N/A
R
MultistateValue
1
TmpOvrRide
W
(1) 1F/0.5C; (2) 2F/1C;
(3) 3F/1.5C; (4) 4F/2C;
(5) 5F/2.5C; (6) 6F/3C;
(7) 7F/3.5C; (8) 8F/4C;
(9) 9F/4.5C; (10) 10F/5C;
(11) No Limit
R
MultistateValue
2
KeyLock
W
(1) NONE; (2) PARTIAL; (3) FULL
R
MultistateValue
3
SystemType
W
(1) CONVEN; (2) HEAT P
R
MultistateValue
4
AuxOut1
W
(1) Humid; (2) Dehumid;
(3) Occupied; (4) AirQual;
(5) EconEn; (6) Not Used
R
MultistateValue
5
AuxOut2
W
(1) Humid; (2) Dehumid;
(3) Occupied; (4) AirQual;
(5) EconEn; (6) Not Used
R
MultistateValue
6
AuxOut3
W
(1) Humid; (2) Dehumid;
(3) Occupied; (4) AirQual;
(5) EconEn; (6) Not Used
R
MultistateValue
7
Input1
W
(1) InTemRem; (2) InTemAvg;
(3) Sup Temp; (4) Ret Temp;
(5) Out Temp; (6) Hum 0-10;
(7) CO2 0-10; (8) Occ DI;
(9) Fault; (10) Not Used
R
MultistateValue
8
Input2
W
(1) InTemRem; (2) InTemAvg;
(3) Sup Temp; (4) Ret Temp;
(5) Out Temp; (6) Hum 0-10;
(7) CO2 0-10; (8) Occ DI;
(9) Fault; (10) Not Used
R
MultistateValue
9
Input3
W
(1) InTemRem; (2) InTemAvg;
(3) Sup Temp; (4) Ret Temp;
(5) Out Temp; (6) Hum 0-10;
(7) CO2 0-10; (8) Occ DI;
(9) Fault; (10) Not Used
R
MultistateValue
10
Input4
W
(1) InTemRem; (2) InTemAvg;
(3) Sup Temp; (4) Ret Temp;
(5) Out Temp; (6) Hum 0-10;
(7) CO2 0-10; (8) Occ DI;
(9) Fault; (10) Not Used
R