User Manual

Application 14900 Point Database
30
Siemens Industry, Inc.
Application Note, App 14900
Object Type
1
Object
Instance
(Point
Number)
Object Name
(Descriptor)
Factory
Default
(SI Units)
2
Eng Units
(SI Units)
State Text
Enumerations/Notes
MultistateValue
10
Input4
10
InTemRem, InTemAvg,
Sup Temp, Ret Temp,
Out Temp, Hum 0-10,
CO2 0-10, Occ DI, Fault,
Not Used
MultistateValue
11
TmpIn1Type
1
Type2Th, 0-10V
MultistateValue
12
TmpIn2Type
1
Type2Th, 0-10V
MultistateValue
13
TmpIn3Type
1
Type2Th, 0-10V
MultistateValue
14
TmpIn4Type
1
Type2Th, 0-10V
MultistateValue
15
StgDifCl
1
1F/0.5C, 2F/1C,
3F/1.5C, 4F/2C,
5F/2.5C, 6F/3C,
7F/3.5C, 8F/4C,
9F/4.5C, 10F/5C
MultistateValue
16
CoolingDB
1
1F/0.5C, 2F/1C,
3F/1.5C, 4F/2C,
5F/2.5C
MultistateValue
17
StgDifHt
1
1F/0.5C, 2F/1C,
3F/1.5C, 4F/2C,
5F/2.5C
MultistateValue
18
HeatingDB
1
1F/0.5C, 2F/1C,
3F/1.5C, 4F/2C,
5F/2.5C
MultistateValue
19
BaudRate
7
9600, 19200, 38400,
57600, 76800, 115200,
Auto
MultistateValue
20
SchEditMode
2
7 days, 5+2, 5+1+1,
Individ, disable
MultistateValue
21
HpCompLock
1
Off, 15F/9C,
20F/7C, 25F/4C,
30F/1C, 35F/2C,
40F/4C, 45F/7C
Present, but no impact on
the control sequence.
MultistateValue
22
HpAuxLock
1
Off, 40F/4C,
45F/7C, 50F/10C,
55F/13C, 60F/16C
Present, but no impact on
the control sequence.
MultistateValue
23
HeatCoolMode
4
COOLING, HEATING,
AUTO, Off
The factory
Relinquish_Default value is
OFF. If AUTO or another
default value is preferred,
set it appropriately.
MultistateValue
24
SchedMode
1
Comfort, Economy,
Protect
MultistateValue
25
ModeEff
1
COOLING, HEATING,
Off