User Manual

Application 14900 Point Database
29
Siemens Industry, Inc.
Application Note, App 14900
Object Type
1
Object
Instance
(Point
Number)
Object Name
(Descriptor)
Factory
Default
(SI Units)
2
Eng Units
(SI Units)
State Text
Enumerations/Notes
BinaryValue
22
SrvcFilter
0
No Serv/Service
BinaryValue
23
HpCompLockOn
0
No Lock/Lock
Present, but no impact on
the control sequence.
BinaryValue
24
HpAuxLockOn
0
No Lock/Locke
Present, but no impact on
the control sequence.
BinaryValue
25
OverCurrent
0
Off/On
BinaryValue
26
SchOcupy
1
No/Yes
BinaryValue
27
HmiOcupy
0
No/Yes
BinaryValue
28
VntlationEff
0
Off/On
BinaryValue
29
PrePurgeEn
0
Off/On
MultistateValue
0
Periods
1
6 Prds
MultistateValue
1
TmpOvrRide
11
1F/0.5C, 2F/1C,
3F/1.5C, 4F/2C,
5F/2.5C, 6F/3C,
7F/3.5C, 8F/4C,
9F/4.5C, 10F/5C,
No Limit
MultistateValue
2
KeyLock
1
NONE, PARTIAL, FULL
MultistateValue
3
SystemType
1
CONVEN,HEAT P
MultistateValue
4
AuxOut1
6
Humid, Dehumid,
Occupied, AirQual,
EconEn, Not Used
MultistateValue
5
AuxOut2
6
Humid, Dehumid,
Occupied, AirQual,
EconEn, Not Used
MultistateValue
6
AuxOut3
6
Humid, Dehumid,
Occupied, AirQual,
EconEn, Not Used
MultistateValue
7
Input1
10
InTemRem, InTemAvg,
Sup Temp, Ret Temp,
Out Temp, Hum 0-10,
CO2 0-10, Occ DI, Fault,
Not Used
MultistateValue
8
Input2
10
InTemRem, InTemAvg,
Sup Temp, Ret Temp,
Out Temp, Hum 0-10,
CO2 0-10, Occ DI, Fault,
Not Used
MultistateValue
9
Input3
10
InTemRem, InTemAvg,
Sup Temp, Ret Temp,
Out Temp, Hum 0-10,
CO2 0-10, Occ DI, Fault,
Not Used