User Manual

Application 14900 Point Database
28
Siemens Industry, Inc.
Application Note, App 14900
Object Type
1
Object
Instance
(Point
Number)
Object Name
(Descriptor)
Factory
Default
(SI Units)
2
Eng Units
(SI Units)
State Text
Enumerations/Notes
AnalogValue
49
OutDoorTmp
0.0
DegF/DegC
If Input1-4 = 5, this is
runtime value.
AnalogValue
50
IndoorTmpAvg
0.0
DegF/DegC
If Input1-4 = 2, this is an
intermediate value.
AnalogValue
51
Humidity
0.0
%RH
If Input1-4 = 6, this is a
runtime value.
AnalogValue
52
IndoorTmpEff
0.0
DegF / DegC
If Input1-4 = 1 or 2, this is a
runtime value.
AnalogValue
53
FanRunTime
0.0
Minutes
BinaryValue
0
FanMode
0
Auto/Manual
BinaryValue
1
RevValveMode
0
Cooling/Heating
BinaryValue
2
SemiContFan
0
No/Yes
BinaryValue
3
FanOpr
1
Gas/Electric
BinaryValue
4
Eco_MstEn
0
Disabled/Enable
BinaryValue
5
Eco_MstCtrl
0
Disabled/Enabled
BinaryValue
6
HumidityIndp
0
No/Yes
BinaryValue
7
Changeover
1
Manual/Automatic
BinaryValue
8
ClockFormat
0
12-hour/24-hour
BinaryValue
9
AckService
0
NoAction/Clear
BinaryValue
10
Units
0
DegF/DegC
BinaryValue
11
DST
0
Disabled/Enabled
BinaryValue
12
SpDispMode
0
Absolute/Relative
BinaryValue
13
OcupyInput
0
Unocc/Occ
BinaryValue
14
HmdyOn
14
Off/On
BinaryValue
15
DeHmdyOn
0
Off/On
BinaryValue
16
OcupyStatus
1
No/Yes
BinaryValue
17
DCV
0
Off/On
BinaryValue
18
ExtFault
0
Normal/Fault
BinaryValue
19
EcomzrOn
1
Off/On
BinaryValue
20
SrvcUvLamp
0
No Serv/Service
BinaryValue
21
SrvcHmdy
0
No Serv/Service