User Manual
Application 14900 Point Database
27
Siemens Industry, Inc.
Application Note, App 14900
140-1231
2020-02-11
Object Type
1
Object
Instance
(Point
Number)
Object Name
(Descriptor)
Factory
Default
(SI Units)
2
Eng Units
(SI Units)
State Text
Enumerations/Notes
AnalogValue
24
TmpIn3Low
0.0
DegF/DegC
AnalogValue
25
TmpIn3High
120.0
DegF/DegC
AnalogValue
26
TmpIn4Low
0.0
DegF/DegC
AnalogValue
27
TmpIn4High
120.0
DegF/DegC
AnalogValue
28
InstallPW
0000.0
AnalogValue
29
ExpertPW
9999.0
AnalogValue
30
HeatingSp
70.0
DegF/DegC
Effective runtime heating
setpoint.
AnalogValue
31
CoolingSp
75.0
DegF/DegC
Effective runtime cooling
setpoint.
AnalogValue
32
ComfortClgSP
75.0
DegF/DegC
AnalogValue
33
ComfortHtgSP
70.0
DegF/DegC
AnalogValue
34
EconClgSP
82.0
DegF/DegC
AnalogValue
35
EconHtgSP
62.0
DegF/DegC
AnalogValue
36
CoolStg
2
AnalogValue
37
PreOcpyPrg
0.0
Hours
AnalogValue
38
MS/TP MAC
255
AnalogValue
39
ProtClgSP
104.0
DegF/DegC
AnalogValue
40
ProtHtgSP
40.0
DegF/DegC
AnalogValue
41
UnitNumber
0.0
AnalogValue
42
HEAT LIMIT
95.0
DegF/DegC
AnalogValue
43
COOL LIMIT
50.0
DegF/DegC
AnalogValue
44
APPLICATION
14900.0
Conventional = 14900
(Read Only, write to
SystemType).
AnalogValue
45
IndoorTmpRmt
0.0
DegF/DegC
If Input1-4 = 1, this is an
intermediate value.
AnalogValue
46
CO2
0.0
Ppm
If Input1-4 = 7, this is a
runtime value.
AnalogValue
47
SupplyTmp
0.0
DegF/DegC
If Input1-4 = 3, this is a
runtime value.
AnalogValue
48
ReturnTmp
0.0
DegF/DegC
If Input1-4 = 4, this is a
runtime value