User Manual

Application 14900 Point Database
26
Siemens Industry, Inc.
Application Note, App 14900
Object Type
1
Object
Instance
(Point
Number)
Object Name
(Descriptor)
Factory
Default
(SI Units)
2
Eng Units
(SI Units)
State Text
Enumerations/Notes
BinaryOutput
3
7
AuxOutput2
0
RelayOff/Relay On
OUT2
BinaryOutput
3
8
AuxOutput3
0
RelayOff/Relay On
OUT3
AnalogValue
0
HmdySp
25.0
%RH
If AuxOut1-3 = 1, this is a
runtime humidity setpoint.
AnalogValue
1
DeHmdySp
50.0
%RH
If AuxOut1-3 = 2, this is a
runtime dehumidification
setpoint.
AnalogValue
2
CO2Setpoint
1000.0
Ppm
If AuxOut1-3 = 4 and Input1-
4 = 7, this is a runtime CO2
setpoint.
AnalogValue
3
ChgOvrDB
5.0
DegF/DegC
AnalogValue
4
TmpOffset
0.0
DegF/DegC
AnalogValue
5
ChgOvrDly
10.0
Minutes
AnalogValue
6
MinOnTimeHt
3.0
Minutes
AnalogValue
7
MinOffTimeHt
5.0
Minutes
AnalogValue
8
MinOffTimeCl
5.0
Minutes
AnalogValue
9
MinOnTimeCl
3.0
Minutes
AnalogValue
10
OccMinRun
30.0
Minutes
AnalogValue
11
StgDlyHt
5.0
Minutes
AnalogValue
12
StgDlyCl
5.0
Minutes
AnalogValue
13
HeatStg
2.0
AnalogValue
14
AuxHeatStg
0.0
AnalogValue
15
HrsOvrRide
2.0
Hours
Present, but no impact on
the control sequence.
AnalogValue
16
UvLampSrvc
0.0
Days
AnalogValue
17
HmdfrSrvc
0.0
Days
AnalogValue
18
FilterSrvc
0.0
Days
AnalogValue
19
BackLight
15.0
Seconds
AnalogValue
20
TmpIn1Low
0.0
DegF/DegC
AnalogValue
21
TmpIn1High
120.0
DegF/DegC
AnalogValue
22
TmpIn2Low
0.0
DegF/DegC
AnalogValue
23
TmpIn2High
120.0
DegF/DegC