User Manual

BACnet Scheduler
24
Siemens Industry, Inc.
Application Note, App 14900
BACnet Scheduler
The thermostat’s Scheduler functionality can be manually configured using the P107
SCHEDULER in the Wizard/Installer menu. This parameter simplifies the task of
entering the local schedule using the touchscreen interface for cases where a day’s
schedule may be identical to another day’s schedule. The local schedule can be
disabled by setting P107 = OFF.
By setting P107 = 1, all days will contain the same schedule.
By setting P107 = 2, Monday through Friday will share a schedule and Saturday
through Sunday will share another schedule.
By setting P107 = 3, Monday through Friday will share a schedule, Saturday and
Sunday will each have a unique schedule.
By setting P107 = 7, all seven days of the week will have individual schedules.
When editing a schedule through the local touchscreen interface, up to six events can
be defined per schedule using the Scheduler menu. When editing a schedule over the
BACnet network, the client simply needs to write to the Weekly_Schedule property of
Schedule instance 0, WeeklySchedule_1.
NOTES:
1. When the schedule is edited using the BACnet network, P107 will be set to 7.
2. The local schedule will write to MultistateValue Instance 24, SchedMode.
This object may be overridden using the network to affect a “temporary exception
mode”. Valid states include: Comfort (1), Economy (2) and Protection (3). The
corresponding setpoints for each mode are set using AnalogValue instance 32,
ComfortClgSP, AnalogValue instance 33, ComfortHtgSP, AnalogValue instance 34,
EconClgSP, AnalogValue instance 35, EconHtgSP, AnalogValue instance 39,
ProtClgSP and AnalogValue instance 40, and ProtHtgSP. Local overrides will occur
for a user-defined duration using the thermostat’s touchscreen interface. The local
override will impact the effective runtime setpoints AnalogValue 30, HeatingSp and
AnalogValue 31, CoolingSp.
NOTES:
1. If an Occupancy sensor is configured, the Present_Value of the BinaryInput is
evaluated after SchedMode’s Priority_Array arbitration, so the effective runtime
operating mode MultistateValue 26, RM OP MODE, will ultimately indicate Comfort if
the BinaryInput is active; otherwise, the Present_Value of SchedMode will take
effect.
2. The RDY2000BN does not support BACnet schedule features such as exception
schedules. Tridium Niagara users must set those unsupported parameters to Skip
Write before importing the schedule objects from the unit for editing. After editing, the
parameters can be downloaded to the RDY2000BN. If Skip Write is not marked for
those unsupported parameters, an error message displays that the writing failed.