User Manual

Sequence of Operation
Auxiliary Sequences
17
Siemens Industry, Inc.
Application Note, App 14900
Figure 3: Wiring Schematic, Conventional.
Auxiliary Sequences
The RDY2000BN primary sequences are designed to control single and multi-stage
heating/cooling systems to maintain a user-defined temperature setpoint.
The following auxiliary sequences are available to optimize occupant comfort and
system efficiency:
Humidification
If one of the configurable digital outputs is configured for a humidification function, the
corresponding relay will close and enable a 24 Vac output signal to be transmitted to
the humidification device. Humidification and dehumidification relays, if configured as
such, cannot be energized simultaneously.
The humidification relay (monitored through HmdyOn) will be energized when
measured humidity drops approximately 4% below setpoint (HmdySp) and will be
de-energized when measured humidity reaches setpoint. Deadbands and proof
timers are in force to prevent short cycling. The thermostat controls humidification
only in Heating mode.
You must enter a humidity setpoint (HmdySp). The valid range is 10 to 90%; the
default value is 25%. If the humidity drops to 4% below setpoint, a 30-second proof
timer engages. If the humidity is still 4% below the setpoint after the proof timer
times out, the humidification relay energizes.