Sequence of Operation
Operation Diagram RTU with Three Cooling Stages and Three Heating Stages.
15
Siemens Industry, Inc.
Application Note, App 14900
If HTG STG NUMBER = 3, the application controls HTG STG 3 (O/B) as follows:
If IndoorTempEff is less than the switching on point of the third heating stage
(HeatingSp 1/2 HeatingDB StgDifHt*2), the third heating stage has been OFF
for at least the time set in MIN OFF, and the Inter-stage Delay (StgDlyHt) timer
has expired, HTG STG 3 (O/B) is turned ON.
If IndoorTempEff is greater than the switching off point of the third heating stage
(HeatingSp + 1/2 HeatingDB StgDifHt*2), and the third heating stage has been
ON for at least the time set in MIN ON, HTG STG 3 (O/B) is turned OFF.
Operation Diagram RTU with Three Cooling Stages
and Three Heating Stages.
Figure 2: RTU with Three Cooling Stages and Three Heating Stages.
Fan Operation
AUTO Mode The fan relay is energized upon a call for heating or cooling per the
operating sequence. When there is no demand for heating or cooling (none of
heating/cooling stages are activated) the fan relay is de-energized.
The fan will turn ON when one of the following conditions has been met:
In Heating mode, when the compressor or stage of electric heat is ON.
In Cooling mode, 15 seconds before the first stage of cooling is energized.
The fan will turn OFF only after the following condition has been met:
The compressor and stages of electric heat have been OFF for at least 30
seconds.