Sequence of Operation
Control Temperature Setpoints
10
Siemens Industry, Inc.
Application Note, App 14900
Sequence of Operation
The following paragraphs show the sequence of operation for Application 14900.
Control Temperature Setpoints
This application has a number of different room temperature setpoints
(ComfortHtgSP, EconHtgSP, ComfortClgSP, and EconClgSP). The setpoint can be
temporarily overridden for a period of time (default is 30 minutes). The application
controls using the effective setpoint (EFF STPT). EFF STPT is set to different values
depending on its HVAC Mode (Cooling, Heating, or Neutral), override status, and the
time of day.
CoolingSp : Cooling Setpoint
CoolingDB: Cooling Deadband
CoolingDB is divided equally above and below CoolingSp; therefore, (CoolingSp +
1/2 CoolingDB) is the switching on point of the first cooling stage, and (CoolingSp
1/2 CoolingDB) is the switching off point of the first cooling stage.
HeatingSp: Heating Setpoint
HeatingDB: Heating Deadband
HeatingDB is divided equally above and below HeatingSp; therefore, (HeatingSp
1/2 HeatingDB) is the switching on point of the first heating stage, and (HeatingSp +
1/2 HeatingDB) is the switching off point of the first heating stage.
StgDifCl: Cooling Inter-stage Differential
(CoolingSp + 1/2 CoolingDB+ StgDifCl) is the switching on point of the second
cooling stage, and (CoolingSP 1/2 CoolingDB+ StgDifCl) is the switching off point
of the second cooling stage.
StgDifHt: Heating Inter-stage Differential
(HeatingSp 1/2 HeatingDB StgDifHt) is the switching on point of the second
heating stage, and (HeatingSp + 1/2 HeatingDB StgDifHt) is the switching off point
of the second heating stage.
CLG SPAN: Cooling SPAN combined ∆T of all stages of cooling,
CLG SPAN is derived from other parameters. For single-stage cooling: CLG SPAN =
CoolingDB; For multi-stage cooling: CLG SPAN = CoolingDB + StgDifCl*n (where n
represents the number of stages of additional cooling.)
HTG SPAN: Heating SPAN combined ∆T of all stages of heating, HTG SPAN is
derived from other parameters. For single-stage heating: HTG SPAN = HeatingDB;
For multi-stage heating: HTG SPAN = HeatingDB + StgDifHt*n (where n represents
the number of stages of additional heating.)
CLG SPAN or HTG SPAN indicates how the bias between room temperature and room
setpoint could possibly be due to the characteristic of hysteresis control.