User Manual
Document No. 125-1009
Installation Instructions
April 27, 2020
Siemens Industry, Inc. Page 9 of 21
Table 3. 100 Series Parameters.
Parameter
Definition
Display
Value
Range
Default
Extended Definition
Notes
P101*
System Type
SYS TYPE
CO(1)
HP(2)
CO
CO = Conventional
HP = Heat Pump
P102*
Cooling
Stages
COOL STGS
0
1
2
3
2
Sets number of cooling stages
P103*
Heating
Stages
HEAT STGS
0
1
2
3
2
Sets number of heating stages
P104*
Aux Heating
Stages
AUX HT STG
0
1
2
0
Sets number of auxilary heat stages
P105*
Fan Operation
HTG FAN
ELE
gAS
ELE
ELE = Fan Relay energized on call for
heat
gAS = Fan Relay always energized
unless Aux Heat calls for heat.
P106*
Reversing
Valve
REV VALVE
0
b
0
0 = Energize reversing valve on cooling
b = Energize reversing valve on heating
~ This parameter only
appears if system is
heat pump
P107*
Scheduler
Days
SCHEDULER
1
2
3
7
OFF
2
1 = Schedule all days with same schedule
2 = One schedule for M-F and another for
Sat + Sun
3 = One schedule for M-F, Sat + Sun
scheduled individually
7 = Schedule each day individually
OFF = Scheduler Disabled
P109*
Units
UNITS
F
C
F
P110
Changeover
AUTO CHNGE
YES
NO
YES
~ This parameter does
not appear on systems
that are heat only or
cool only
P111
Changeover
Deadband
DEADBAND
3
4
5
6
7
8
9
5°F
Deadband in degrees F
~ This parameter does
not appear if
CHANGEOVER = M
~ This parameter does
not appear on systems
that are heat only or
cool only
P112
Daylight
Savings
DAYLT SAVE
YES
NO
NO
Y = Auto adjust for daylight savings time
N = Does not auto adjust for daylight
savings time
P113
Display Temp
Setpoint
TMP SP DIS
0=Absolute
1=Relative
0=Absolute
Selection of setpoint display: absolute or
relative value
* Included in Set-up Wizard