Table 4. 200 Series Parameters.
Parameter
Definition
Display
Value Range
Default
Extended Definition
Notes
P201
Heat Temp
Limit
HEAT LIMIT
45 - 95
95°F
Sets maximum allowable heating
setpoint
~ Does not appear if HEAT
STAGES = 0
P202
Cool Temp
Limit
COOL LIMIT
50 - 95
50°F
Sets minimum allowable cooling set
point
~ Does not appear if COOL
STAGES = 0
P203
Temperature
Display
Offset
TMP OFFSET
-5 to +5
0°F
Enables adjustment of control temp and
display temp in 1-degree increments.
Applies only to onboard temp sensor.
Indoor temp only.
~ Do not adjust until in
operation for at least 1 hour.
P204
Override
Time Limit
HRS OVR RD
"---" = unlimited;
0 = none;
2 =2 hours;
4 = 4 hours;
6 = 6 hours;
8 = 8 hours
10 = 10 hours
12 = 12 hours
24 = 24 hours
96=96 hours
2
Number of hours that scheduled
setpoint can be manually overridden.
0 = no override allowed
~ This parameter does not
appear if SCHEDULER =
OFF
P205
Override
Temp Limit
TMP OVR RD
---
1
2
3
4
5
6
7
8
9
10
---
Number of degrees F that are allowed
above or below scheduled setpoint.
--- = Unlimited
~ This parameter does not
appear if SCHEDULER =
OFF
P206
Heat Pump
Compressor
Lock Out
HP COMP LO
OFF
15=15°F
20=20°F
25=25°F
30=30°F
35=35°F
40=40°F
45=45°F
OFF
Heat pump compressor will not operate
below this outdoor temp -- forcing unit
to auxiliary heat
~ Only shown if SYS TYPE =
HP with AUX HEAT and there
is an outdoor temp sensor
~ Must be lower than HP
AUX LO
P207
Heat Pump
Auxiliary
Heat Lockout
HP AUX LO
OFF
40=40°F
45=45°F
50=50°F
55=55°F
60=60°F
OFF
Heat pump auxiliary heat will not
operate above this outdoor temp.
~ Only shown if SYS TYPE =
HP with AUX HEAT and there
is an outdoor temp sensor
~ Must be higher than HP
COMP LO
P208
Service UV
Lamp
UV LAMP
0-365
0
Number of days until SERVICE UV
LAMP message is displayed.
0 = function disabled.
P209
Service
Humidifier
HMDFR
SRVC
0-365
0
Number of days until SERVICE
HUMIDIFIER message is displayed.
0 = function disabled.
P210
Service Air
Filter
FLTR SRVC
0-365
0
Number of days until SERVICE AIR
FILTER message is displayed.
0 = function disabled.
P211
Keypad
Lockout
KEY LOCK
OFF
2
3
OFF
OFF = No lockout
2 = Partial Lockout (only temp setpoint
can be adjusted)
3= Total Lockout
P212
Clock Format
CLOCK
12
24
12
12 = 12-hour format
24 = 24-hour format