User Manual

Managing application settings
6
24 | 30 A6V11214854_enUS_a
No.
Application
settings
Descriptions
Factory
settings
Range Dependencies
41.
Changeover
delay for
heating/cooling
The minimum off
time before
switching between
heating and cooling.
300 s 30…600 s
Heat pump
must be
selected as the
equipment type.
42.
HP
compressor
min. ON time
Minimum run time
for compressor(s) in
heat pump systems.
3 min 0…60 min
43.
HP
compressor
min. OFF time
Minimum off time for
compressor(s) in
heat pump systems.
3 min 0…60 min
44.
Heating min.
ON time
The minimum run
time for the heating
system.
5 min 3…15 min
45.
Heating min.
OFF time
The minimum off
time for the heating
system.
5 min 3…15 min
46.
Cooling min.
ON time
The minimum run
time for the cooling
system
5 min 3…15 min
47.
Cooling min.
OFF time
The minimum off
time for the cooling
system
5 min 3…15 min
48.
Humidifier
(fan) min. ON
time
The minimum run
time for the
humidifier
3 min 0…60 min
The output
must have been
configured as a
humidifier.
49.
Humidifier
(fan) min. OFF
time
The minimum off
time for the
humidifier
3 min 0…60 min
50.
Dehum. (fan)
min. ON time
The minimum run
time for the
dehumidifier
3 min 0…60 min
The output
must have been
configured as a
dehumidifier.
51.
Dehum. (fan)
min. OFF time
The minimum off
time for the
dehumidifier
3 min 0…60 min