User Manual
Managing a
pplication settings
6
22 | 30 A6V11214854_enUS_a
No.
Application
settings
Descriptions
Factory
settings
Range
Dependencie
s
26.
Comfort air
quality
setpoint
Scheduled air quality
setpoint when space is
occupied. This setpoint
must be lower than
that for Protection.
900 ppm 0…2000 ppm
Displays only
if the output is
configured as
an outside air
damper in
section
Changing
system setup
[➙ 14].
27.
Economy
air quality
setpoint
Scheduled air quality
setpoint during
transition from
Unoccupied to
Comfort. This setpoint
must be lower than
that for Protection.
1100 ppm 0…2000 ppm
28.
Unoccupied
air quality
setpoint
Scheduled air quality
setpoint when space is
unoccupied.
1500 ppm 0…2000 ppm
29.
Protection
air quality
setpoint
The air quality setpoint
if the operating mode
is OFF and Protection
is enabled.
1500 ppm 0…2000 ppm
No.
Application
settings
Descriptions
Factory
settings
Range Dependencies
30.
Humidity
control in
heating only
Humidification allowed
only when heating
system is energized.
No N/A
The output
must be
configured as a
humidifier.
31. Free cooling
Enables free cooling by
opening the outside air
damper.
No N/A
The output
must be
configured as
an outside air
damper.
32.
Room
presence
detector
The thermostat
switches from
Unoccupied to Comfort
when occupancy is
detected.
Active N/A N/A
Room air quality setpoints
Functions