User Manual
Managing application settings
6
A6V11214854_enUS_a 19 | 30
No.
Application
settings
Descriptions
Factory
settings
Range Dependencies
12.
Comfort
cooling
setpoint
Scheduled cooling
setpoint when space is
occupied. This setpoint
must be higher than all
the heating setpoints
and lower than the
cooling setpoint for
Protection.
75 °F
(24 ℃)
32…122 F
(0…50 ℃)
N/A
13.
Economy
cooling
setpoint
Scheduled cooling
setpoint during
transition from
Unoccupied to Comfort.
This setpoint must be
higher than all the
heating setpoints and
lower than the cooling
setpoint for Protection.
77 °F
(25 ℃)
32…122 F
(0…50 ℃)
N/A
14.
Unoccupied
cooling
setpoint
Scheduled cooling
setpoint when space is
unoccupied. This
setpoint must be higher
than all the heating
setpoints and lower
than the cooling
setpoint for Protection.
86 °F
(30 ℃)
32…122 F
(0…50 ℃)
N/A
15.
Protection
cooling
setpoint
Cooling setpoint if the
operating mode is OFF
and Protection is
enabled. This setpoint
must be higher than all
the heating setpoints.
95 °F
(35 ℃)
32…122 F
(0…50 ℃)
This setpoint is
valid only if the
default option is
selected for
Application
setting No. 57.
16.
Min. cooling
setpoint
cool.
Minimum allowable
cooling setpoint.
45 °F
(7 ℃)
32…122 F
(0…50 ℃)
The cooling
protection
setpoint is valid
only if the
default option is
selected for
Application
setting No. 57.
Cooling setpoints