User Manual

Managing application settings
6
18 | 30 A6V11214854_enUS_a
No.
Application
settings
Descriptions
Factory
settings
Range Dependencies
7.
Comfort
heating
setpoint
Scheduled heating
setpoint when space is
occupied. This setpoint
must be higher than
that for Protection.
70 °F
(21 )
32…122 °F
(0…50 )
N/A
8.
Economy
heating
setpoint
Scheduled heating
setpoint during
transition from
Unoccupied to Comfort.
This setpoint must be
higher than that for
Protection.
66 °F
(19 )
32…122 °F
(0…50 )
N/A
9.
Unoccupied
heating
setpoint
Scheduled heating
setpoint when space is
unoccupied. This
setpoint must be higher
than that for Protection.
59 °F
(15 )
32…122 °F
(0…50 )
N/A
10.
Protection
heating
setpoint
Heating setpoint if the
operating mode is OFF
and Protection is
enabled.
45°F
(7 )
32…122 °F
(0…50 )
This setpoint is
valid only if the
default option is
selected for
Application
setting No. 57.
11.
Max.
heating
setpoint
Maximum allowable
heating setpoint.
95°F
(35 )
32…122 °F
(0…50 )
Heating setpoints