User Manual
Managing application settings
6
A6V11214854_enUS_a 17 | 30
6 Managing application settings
NOTE:
● Parameter availability depends on your selected application for the thermostat.
● Numbers marked in the following tables are only for easy readability in this
document. They don't represent the parameter numbers in the local thermostat.
No.
Application
settings
Descriptions
Factory
settings
Range
Dependencie
s
1.
X1 room
temp. ref. at
0V
Calibrates thermostat to
low end of temperature
sensor signal (for
example, 0 V = 32 ℉)
32 °F
(0 ℃)
-58…176 °F
(-50…80 °C)
A DC 0 to
10 V external
room
temperature
sensor must
be connected
with the
thermostat
using terminal
X1.
2.
X1 room
temp. ref. at
10V
Calibrates thermostat to
high end of temperature
sensor signal (for
example, 10 V =
122 ℉)
122 °F
(50 ℃)
-58…176 °F
(-50…80 °C)
3.
X2 room
temp. ref. at
0V
Calibrates thermostat to
low end of temperature
sensor signal (for
example, 0 V = 32 ℉)
32 °F
(0 ℃)
-58…176 °F
(-50…80 °C)
A DC 0 to
10 V external
room
temperature
sensor must
be connected
with the
thermostat
using terminal
X2.
4.
X2 room
temp. ref. at
10V
Calibrates thermostat to
high end of temperature
sensor signal (for
example, 10 V =
122 ℉)
122 °F
(50 ℃)
-58…176 °F
(-50…80 °C)
5.
Outside
temp. ref. at
0V
Calibrates thermostat to
low end of temperature
sensor signal (for
example, 0 V = -58 ℉)
-58 °F
(-50 ℃)
-58…176 °F
(-50…80 °C)
A DC 0 to
10 V external
outside air
temperature
sensor must
be connected.
6.
Outside
temp. ref. at
10V
Calibrates thermostat to
high end of temperature
sensor signal (for
example, 10 V =
176 ℉)
176 °F
(80 ℃)
-58…176 °F
(-50…80 °C)
Multi-functional inputs