11/23/2021
Inputs, Continued
Connections to Multifunctional Inputs X1 - M - X2
Active DC 0 V to 10 V sensors
- Room temperature range
(default)
- Outdoor temperature range
(default)
- Humidity range (default)
- CO
2
range (default)
NOTE: min./max. configurable via parameters
32 °F to 122 °F (0 to 50 °C)
-32 °F to 176 °F (-50 to 80 °C)
0 to 100%
0 to 2000 ppm
Digital contacts
- Operating action
- Contact sensing
- Parallel connection
- Input function
Selectable N.O./N.C.
DC 14 to 40 V, 8 mA (typical)
Max. 20 thermostats per switch
Selectable
Outputs
Relay Contact Capacity
Voltage
AC 24 V (±20%)
Current
Min. 0.02 A, Max. 1 A per output
Operational Data
Setpoint Range
45 °F to 95 °F (7 °C to 35 °C)
Built-in Room Temperature Sensor
Temperature range
Accuracy at 77 °F (25 °C)
Display resolution
32 °F to 122 °F
±0.9 °F or 0.5 °C
1 °F (0.5 °C)
Built-in Room Humidity Sensor
Humidity range
Accuracy at 77 °F (25 °C)
Display resolution
0% to 100%
± 5% r.h.
1%