Commissioning Instructions
Appendices
8
56 | 61
A6V11214854_enUS_
c
Obj.
No.
Obj. Name
Obj. Name
Base
Description
Obj.
Identifier
Data
Type
Sig. Type
Unit
Resolution
Max.
Value
Min.
Value
Change
of Value
State No.
State Text
Present
Value
Default
Command
327
%R%'RHvac
Coo'GrnLf'R
HvacEei
RHvacEei
Room energy
efficiency
indication
HVAC
19,78
Multistat
e Value
~
~
~
~
~
~
5
1=Undefined
2=Poor
3=Satisfactor
y 4=Good
5=Excellent
Undefined
~
328
%R%'RHvac
Coo'HuDhuS
taDtr'HuDhu
Sta
HuDhuSta
Humidification/
dehumidificatio
n state
19,79
Multistat
e Value
~
~
~
~
~
~
3
1=Neither
2=Humidify
3=Dehumidify
Neither
~
329
%R%'RHvac
Coo'HCStaD
tr'HCSta
HCSta
Heating/cooling
state
19,80
Multistat
e Value
~
~
~
~
~
~
3
1=Neither
2=Heating
3=Cooling
Neither
~
330
%R%'RHvac
Coo'RAQualI
nd
RAQualInd
Room air
quality
indication
19,87
Multistat
e Value
~
~
~
~
~
~
4
1=Undefined
2=Poor
3=Okay
4=Good
Undefined
~
331
%R%'HVAC'
HCcl'HpuSta
HpuSta
Heat pump
state
19,95
Multistat
e Value
~
~
~
~
~
~
3
1=Off
2=Heating
3=Cooling
Off
~
332
%R%'HVAC'
HCcl'HpuSta
HpuSta
Heat pump
state
19,93
Multistat
e Value
~
~
~
~
~
~
3
1=Off
2=Heating
3=Cooling
Off
~
333
%R%'HVAC'
HCDevOut'H
clDevTyp
HclDevTyp
Heating coil
device type
19.114
Multistat
e Value
~
~
~
~
~
~
7
1=None
2=Electric 1-
stage
3=Electric 2-
stage
4=Electric 3-
stage 5=Gas
1-stage
6=Gas 2-
stage 7=Gas
3-stag
None
~
334
%R%'HVAC'
HCDevOut'H
CclDevTyp
HCclDevTyp
Heating/cooling
coil device type
19.115
Multistat
e Value
~
~
~
~
~
~
3
1=None
2=Heat pump
1-stage
3=Heat pump
2-stage
None
~
335
%R%'HVAC'
HCDevOut'C
clDevTyp
CclDevTyp
Cooling coil
device type
19.116
Multistat
e Value
~
~
~
~
~
~
3
1=None
2=DX 1-stage
3=DX 2-stage
None
~