Commissioning Instructions

Appendices
A6V11214854_enUS_
c
55 | 61
8
Obj.
No.
Obj. Name
Obj. Name
Base
Description
Obj.
Identifier
Data
Type
Sig. Type
Unit
Resolution
Max.
Value
Min.
Value
Change
of Value
State No.
State Text
Present
Value
Default
Command
vMod
open
323
%R%'HVAC'
DhumFrsd'D
humFrsdDev
Mod
DhumFrsdD
evMod
Dehumidifier
free-standing
device mode
19.104
Multistat
e Value
~
~
~
~
~
~
3
1=Off
2=Control
mode 3=Fully
open
Null
Off
324
%R%'HVAC'
HumFrsd'Hu
mFrsdDevM
od
HumFrsdDe
vMod
Humidifier free-
standing device
mode
19.105
Multistat
e Value
~
~
~
~
~
~
3
1=Off
2=Control
mode 3=Fully
open
Null
Off
325
%R%'HVAC'
PrPltOpMod
PrPltOpMod
Present plant
operating mode
19.106
Multistat
e Value
~
~
~
~
~
~
17
1=Off
2=Protection
3=Economy
4=Pre-
Comfort
5=Comfort
6=Warm-up
7=Cool down
8=Room low
temp.prot.
9=Cond.overfl
ow prot.
10=Free
cooling
11=Night
cooling
12=Ventilatio
n
13=Equit.tem
p.prot 14=Air
vol.flow off
15=Not used
16=Not used
17=Not used
Null
Off
326
%R%'CenO
pMod'CenOs
sc'OsscSta
OsscSta
OSSC state
(optimum start
stop control)
19,74
Multistat
e Value
~
~
~
~
~
~
8
1=Setback
2=Early start
3=Late start
4=Early
occupancy
5=Economy
6=Comfort
7=Stop
8=Lact
occupancy
Setbank
~