Commissioning Instructions

Appendices
8
52 | 61
A6V11214854_enUS_
c
Obj.
No.
Obj. Name
Obj. Name
Base
Description
Obj.
Identifier
Data
Type
Sig. Type
Unit
Resolution
Max.
Value
Min.
Value
Change
of Value
State No.
State Text
Present
Value
Default
Command
299
%R%'HclGa
sCmd2St
HclGasCmd
2St
Heating coil
gas command
second stage
4,22
Binary
Output
BO_Relay
_NO
~
~
~
~
~
~
0=Off 1=On
Off
Off
300
%R%'HclGa
sCmd2St
HclGasCmd
2St
Heating coil
gas command
second stage
4,23
Binary
Output
BO_Relay
_NO
~
~
~
~
~
~
0=Off 1=On
Off
Off
301
%R%'RGrnL
f'REei
REei
Energy
efficiency
indication room
19,77
Multistat
e Value
~
~
~
~
~
~
5
1=Undefined
2=Poor
3=Satisfactor
y 4=Good
5=Excellent
Null
Undefined
302
%R%'ROpM
odDtr'ROpM
od
ROpMod
Room
operating mode
19,75
Multistat
e Value
~
~
~
~
~
~
4
1=Protection
2=Unoccupie
d 3=Economy
4=Comfort
Null
Comfort
303
%R%'ROpM
odDtr'OccMo
d
OccMod
Occupancy
mode
19,76
Multistat
e Value
~
~
~
~
~
~
3
1=Off
2=Absent
3=Present
Null
Present
304
%R%'CenO
pMod'CenO
pModCmdv
CenOpModC
mdv
Central
operating mode
command value
19,73
Multistat
e Value
~
~
~
~
~
~
4
1=Protection
2=Unoccupie
d 3=Economy
4=Comfort
Null
Comfort
305
%R%'RHvac
Coo'PscMod
Dtr'HvacPsc
Mod
HvacPscMo
d
HVAC
presence mode
19,83
Multistat
e Value
~
~
~
~
~
~
4
1=None
2=Consider
present
3=Consider
absent
4=Cons.prese
nt & absent
Null
None
306
%R%'RHvac
Coo'PltMod
Dtr'PltOpMo
d
PltOpMod
Plant operating
mode
19,84
Multistat
e Value
~
~
~
~
~
~
17
1=Off
2=Protection
3=Economy
4=Pre-
Comfort
5=Comfort
6=Warm-up
7=Cool down
8=Room low
temp.prot.
9=Cond.overfl
ow prot.
10=Free
Null
Off