Commissioning Instructions
Appendices
8
50 | 61
A6V11214854_enUS_
c
Obj.
No.
Obj. Name
Obj. Name
Base
Description
Obj.
Identifier
Data
Type
Sig. Type
Unit
Resolution
Max.
Value
Min.
Value
Change
of Value
State No.
State Text
Present
Value
Default
Command
271
%R%'EnRPs
cDet
EnRPscDet
Room presence
detector
5.161
Binary
Value
~
~
~
~
~
~
~
0=Closed
1=Open
Closed
~
272
%R%'EnFre
eC
EnFreeC
Free cooling
5.160
Binary
Value
~
~
~
~
~
~
~
0=No 1=Yes
No
~
273
%R%'EnHu
HOnly
EnHuHOnly
Humidity
control in
heating only
5.159
Binary
Value
~
~
~
~
~
~
~
0=No 1=Yes
No
~
274
%R%'HclEl1
StPos
HclEl1StPos
Heating coil
electric pos.first
stage
4,12
Binary
Output
BO_Relay
_NO
~
~
~
~
~
~
0=Off 1=On
Off
Off
275
%R%'HclEl1
StPos
HclEl1StPos
Heating coil
electric pos.first
stage
4,13
Binary
Output
BO_Relay
_NO
~
~
~
~
~
~
0=Off 1=On
Off
Off
276
%R%'HclElP
os
HclElPos
Heating coil
electric position
4,0
Binary
Output
BO_Relay
_NO
~
~
~
~
~
~
0=Off 1=On
Off
Off
277
%R%'HclElP
os
HclElPos
Heating coil
electric position
4,1
Binary
Output
BO_Relay
_NO
~
~
~
~
~
~
0=Off 1=On
Off
Off
278
%R%'Dhum
Cmd
DhumCmd
Dehumidifier
command
4,2
Binary
Output
BO_Relay
_NO
~
~
~
~
~
~
0=Off 1=On
Off
Off
279
%R%'HpuRv
rVlv
HpuRvrVlv
Heat pump
reversing valve
4,3
Binary
Output
BO_Relay
_NO
~
~
~
~
~
~
0=Inactive
1=Active
Inactive
Inactive
280
%R%'HpuC
md2St
HpuCmd2St
Heat pump
command
second stage
4,4
Binary
Output
BO_Relay
_NO
~
~
~
~
~
~
0=Off 1=On
Off
Off
281
%R%'HpuC
md1St
HpuCmd1St
Heat pump
command first
stage
4,5
Binary
Output
BO_Relay
_NO
~
~
~
~
~
~
0=Off 1=On
Off
Off
282
%R%'HpuC
md
HpuCmd
Heat pump
command
4,6
Binary
Output
BO_Relay
_NO
~
~
~
~
~
~
0=Off 1=On
Off
Off
283
%R%'CclDx
2StPos
CclDx2StPo
s
Cooling coil DX
evap.pos.secon
d stage
4,7
Binary
Output
BO_Relay
_NO
~
~
~
~
~
~
0=Off 1=On
Off
Off
284
%R%'CclDx
1StPos
CclDx1StPo
s
Cooling coil DX
evap.pos.secon
d stage
4,8
Binary
Output
BO_Relay
_NO
~
~
~
~
~
~
0=Off 1=On
Off
Off
285
%R%'CclDx
Pos
CclDxPos
Cooling coil DX
evaporator
4,9
Binary
Output
BO_Relay
_NO
~
~
~
~
~
~
0=Off 1=On
Off
Off