Commissioning Instructions
Appendices
A6V11214854_enUS_
c
41 | 61
8
Obj.
No.
Obj. Name
Obj. Name
Base
Description
Obj.
Identifier
Data
Type
Sig. Type
Unit
Resolution
Max.
Value
Min.
Value
Change
of Value
State No.
State Text
Present
Value
Default
Command
heat_US
144
%R%'LockH
clTOaHi
LockHclTOa
Hi
Outdoor temp.
to disable heat
2,226
Analog
Value
~
°C
0.5
20
0
0.1
~
~
0
~
145
%R%'LockH
clTOaHi_US
LockHclTOa
Hi_US
Outdoor temp.
to disable
heat_US
2,482
Analog
Value
~
°F
0.5
68
32
0.1
~
~
0
~
146
%R%'LockH
puTOaLo
LockHpuTO
aLo
HP compressor
lockout low
temp.
2,222
Analog
Value
~
°C
0.5
10
-10
0.1
~
~
0
~
147
%R%'LockH
puTOaLo_U
S
LockHpuTO
aLo_US
HP compressor
lockout low
temp._US
2,478
Analog
Value
~
°F
0.5
50
14
0.1
~
~
0
~
148
%R%'LockH
puTOaLo
LockHpuTO
aLo
HP compressor
lockout low
temp.
2,223
Analog
Value
~
°C
0.5
10
-10
0.1
~
~
0
~
149
%R%'LockH
puTOaLo_U
S
LockHpuTO
aLo_US
HP compressor
lockout low
temp._US
2,479
Analog
Value
~
°F
0.5
50
14
0.1
~
~
0
~
150
%R%'TR1Va
l0V
TR1Val0V
X1 room temp.
ref. at 0V
2,227
Analog
Value
~
°C
0.5
80
-50
0.1
~
~
0
~
151
%R%'TR1Va
l0V_US
TR1Val0V_U
S
X1 room temp.
ref. at 10V_US
2,483
Analog
Value
~
°F
0.5
176
-58
0.1
~
~
0
~
152
%R%'TR1Va
l10V
TR1Val10V
X1 room temp.
ref. at 10V
2,228
Analog
Value
~
°C
0.5
80
-50
0.1
~
~
0
~
153
%R%'TR1Va
l0V_US
TR1Val0V_U
S
X1 room temp.
ref. at 10V_US
2,484
Analog
Value
~
°F
0.5
176
-58
0.1
~
~
0
~
154
%R%'TR2M
svAdj
TR2MsvAdj
X2 temp.
sensor adj.
2,244
Analog
Value
~
K
0.5
5
-5
0.1
~
~
0
~
155
%R%'TR2M
svAdj_US
TR2MsvAdj_
US
X2 temp.
sensor adj._US
2,500
Analog
Value
~
°F
0.5
41
23
0.1
~
~
0
~
156
%R%'TR2M
svAdj
TR2MsvAdj
X2 temp.
sensor adj.
2,245
Analog
Value
~
K
0.5
5
-5
0.1
~
~
0
~
157
%R%'TR2M
svAdj_US
TR2MsvAdj_
US
X2 temp.
sensor adj._US
2,501
Analog
Value
~
°F
0.5
41
23
0.1
~
~
0
~
158
%R%'TR2M
svAdj
TR2MsvAdj
X2 temp.
sensor adj.
2,246
Analog
Value
~
K
0.5
5
-5
0.1
~
~