Commissioning Instructions

Appendices
A6V11214854_enUS_
c
39 | 61
8
Obj.
No.
Obj. Name
Obj. Name
Base
Description
Obj.
Identifier
Data
Type
Sig. Type
Unit
Resolution
Max.
Value
Min.
Value
Change
of Value
State No.
State Text
Present
Value
Default
Command
119
%R%'RHvac
Coo'HuCtl'S
pHuRelRPrt
SpHuRelRPr
t
Protection
humidity
setpoint
2,159
Analog
Value
~
%RH
5
100
0
1
~
~
30
~
120
%R%'RHvac
Coo'DhuCtl'
SpDhuRelR
Cmf
SpDhuRelR
Cmf
Comfort
dehum.
setpoint
2,250
Analog
Value
~
%RH
5
100
0
1
~
~
60
~
121
%R%'RHvac
Coo'DhuCtl'
SpDhuRelR
Pcf
SpDhuRelR
Pcf
Economy
dehum.
setpoint
2,251
Analog
Value
~
%RH
5
100
0
1
~
~
60
~
122
%R%'RHvac
Coo'DhuCtl'
SpDhuRelR
Eco
SpDhuRelR
Eco
Unoccupied
dehum.
setpoint
2,252
Analog
Value
~
%RH
5
100
0
1
~
~
70
~
123
%R%'RHvac
Coo'DhuCtl'
SpDhuRelR
Prt
SpDhuRelR
Prt
Protection
dehum.
setpoint
2,253
Analog
Value
~
%RH
5
100
0
1
~
~
70
~
124
%R%'RHvac
Coo'VntCtl'S
pAQualRCm
f
SpAQualRC
mf
Comfort air
quality setpoint
2,166
Analog
Value
~
ppm
100
2000
0
10
~
~
900
~
125
%R%'RHvac
Coo'VntCtl'S
pAQualRPcf
SpAQualRP
cf
Economy air
quality setpoint
2,167
Analog
Value
~
ppm
100
2000
0
10
~
~
1100
~
126
%R%'RHvac
Coo'VntCtl'S
pAQualREco
SpAQualRE
co
Unoccupied air
quality setpoint
2,168
Analog
Value
~
ppm
100
2000
0
10
~
~
1500
~
127
%R%'RHvac
Coo'VntCtl'S
pAQualRPrt
SpAQualRPr
t
Protection air
quality setpoint
2,169
Analog
Value
~
ppm
100
2000
0
10
~
~
1500
~
128
%R%'RHvac
Coo'TCtlH'S
pHPcf
SpHPcf
Economy
heating setpoint
2,177
Analog
Value
~
°C
0.5
50
0
0
~
~
19
~
129
%R%'RHvac
Coo'TCtlH'S
pHPcf_US
SpHPcf_US
Economy
heating
setpoint_US
2,433
Analog
Value
~
°F
0.5
122
32
0
~
~
66.2
~
130
%R%'RHvac
SpHEco
Unoccupied
2,178
Analog
~
°C
0.5
50
0
0
~
~
15
~