Commissioning Instructions

Appendices
8
38 | 61
A6V11214854_enUS_
c
Obj.
No.
Obj. Name
Obj. Name
Base
Description
Obj.
Identifier
Data
Type
Sig. Type
Unit
Resolution
Max.
Value
Min.
Value
Change
of Value
State No.
State Text
Present
Value
Default
Command
Hcl'HclHReq
heating request
Value
107
%R%'HVAC'
Hcl'HclHReq
HclHReq
Heating coil
heating request
2,216
Analog
Value
~
%
1
100
0
1
~
~
0
~
108
%R%'HVAC'
Hum'HumHu
Req
HumHuReq
Humidifier
humidification
request
2,217
Analog
Value
~
%
1
100
0
1
~
~
0
~
109
%R%'HVAC'
DhumFrsd'D
humFrsdDhu
Req
DhumFrsdD
huReq
Dehumidifier
free-standing
dehmdf.req.
2,218
Analog
Value
~
%
1
100
0
1
~
~
0
~
110
%R%'HVAC'
HumFrsd'Hu
mFrsdHuRe
q
HumFrsdHu
Req
Humidifier free-
standing
hmdf.request
2,219
Analog
Value
~
%
1
100
0
1
~
~
0
~
111
%R%'HVAC'
TREff
TREff
Effective room
temperature
2,220
Analog
Value
~
°C
0.1
50
0
0.1
~
~
0
~
112
%R%'HVAC'
TREff_US
TREff_US
Effective room
temperature_U
S
2,476
Analog
Value
~
°F
0.1
122
32
0.1
~
~
0
~
113
%R%'HVAC'
TOaEff
TOaEff
Effective
outside air
temperature
2,221
Analog
Value
~
°C
0.1
70
-70
0.1
~
~
0
~
114
%R%'HVAC'
TOaEff_US
TOaEff_US
Effective
outside air
temperature_U
S
2,477
Analog
Value
~
°F
0.1
158
-94
0.1
~
~
0
~
115
Infra'AppNr
AppNr
Application
number
2,254
Analog
Value
~
~
0.1
3.40E+38
-3.40E+38
0.1
~
~
0
~
116
%R%'RHvac
Coo'HuCtl'S
pHuRelRCm
f
SpHuRelRC
mf
Comfort
humidity
setpoint
2,156
Analog
Value
~
%RH
5
100
0
1
~
~
40
~
117
%R%'RHvac
Coo'HuCtl'S
pHuRelRPcf
SpHuRelRP
cf
Economy
humidity
setpoint
2,157
Analog
Value
~
%RH
5
100
0
1
~
~
40
~
118
%R%'RHvac
Coo'HuCtl'S
pHuRelREco
SpHuRelRE
co
Unoccupied
humidity
setpoint
2,158
Analog
Value
~
%RH
5
100
0
1
~
~
30
~