Commissioning Instructions

Appendices
8
36 | 61
A6V11214854_enUS_
c
Obj.
No.
Obj. Name
Obj. Name
Base
Description
Obj.
Identifier
Data
Type
Sig. Type
Unit
Resolution
Max.
Value
Min.
Value
Change
of Value
State No.
State Text
Present
Value
Default
Command
80
%R%'RHvac
Coo'TCtlC'Pr
SpCEco_US
PrSpCEco_
US
Present
unoccupied
cooling
setpoint_US
2,445
Analog
Value
~
°F
0.1
122
32
0.1
~
~
0
~
81
%R%'RHvac
Coo'TCtlC'Pr
SpCPrt
PrSpCPrt
Present
protection
cooling setpoint
2,190
Analog
Value
~
°C
0.1
50
0
0.1
~
~
0
~
82
%R%'RHvac
Coo'TCtlC'Pr
SpCPrt_US
PrSpCPrt_U
S
Present
protection
cooling
setpoint_US
2,446
Analog
Value
~
°F
0.1
122
32
0.1
~
~
0
~
83
%R%'RHvac
Coo'RHuRel
RHuRel
Relative
humidity for
room
2,183
Analog
Value
~
%RH
1
100
0
1
~
~
0
~
84
%R%'RHvac
Coo'RAQual
RAQual
Room air
quality
2,184
Analog
Value
~
ppm
1000
5000
0
10
~
~
0
~
85
%R%'RHvac
Coo'RTemp
RTemp
Room
temperature
2,185
Analog
Value
~
°C
0.5
50
0
0.1
~
~
0
~
86
%R%'RHvac
Coo'Rtemp_
US
Rtemp_US
Room
temperature_U
S
2,441
Analog
Value
~
°F
0.5
122
32
0.1
~
~
0
~
87
%R%'RHvac
Coo'HuRelR
Col'HuRelR
Rs
HuRelRRs
Result of
relative
humidity for
room
2,170
Analog
Value
~
%RH
0.1
3.40E+38
-3.40E+38
0.1
~
~
0
~
88
%R%'HVAC'
DmpOa'Dmp
OaCReq
DmpOaCRe
q
Outside air
damper cooling
request
2,195
Analog
Value
~
%
1
100
0
1
~
~
0
~
89
%R%'HVAC'
DmpOa'Dmp
OaVntReq
DmpOaVntR
eq
Outside air
damper
ventilation
request
2,196
Analog
Value
~
%
1
100
0
1
~
~
0
~
90
%R%'HVAC'
Fan'FanVnt
Req
FanVntReq
Fan ventilation
request
2,197
Analog
Value
~
%
1
100
0
1
~
~
0
~
91
%R%'HVAC'
Ccl'CclCReq
CclCReq
Cooling coil
cooling request
2,200
Analog
Value
~
%
1
100
0
1
~
~
0
~
92
%R%'HVAC'
CclDhuReq
Cooling coil
2,201
Analog
~
%
1
100
0
1
~
~
0
~