Commissioning Instructions
Managing application settings
6
24 | 61
A6V11214854_enUS_c
No.
Application
settings
Descriptions
Factory
setting
s
Range
Dependencies
52.
Humidify (no
fan) min. ON
time
The minimum run
time of a
standalone
humidifier. This
minimum limitation
protects the
humidifier from
short cycling.
3 min
0…60 min
The output
must have
been
configured as
Humidifier (no
fan) in
Changing
system setup
[➙ 13].
53.
Humidify (no
fan) min. OFF
time
The minimum OFF
time of a
standalone
humidifier. This
minimum limitation
protects the
humidifier from
short cycling.
3 min
0…60 min
54.
Dehum. (no
fan) min. ON
time
The minimum run
time of a
standalone
dehumidifier. This
minimum limitation
protects the
dehumidifier from
short cycling.
3 min
0…60 min
The output
must have
been
configured as
Dehumidifier
(no fan) in
Changing
system setup
[➙ 13].
55.
Dehum. (no
fan) min. OFF
time
The minimum OFF
time of a
standalone
dehumidifier. This
minimum limitation
protects the
dehumidifier from
short cycling.
3 min
0…60 min