Commissioning Instructions
Managing application settings
6
A6V11214854_enUS_c
23 | 61
No.
Application
settings
Descriptions
Factory
setting
s
Range
Dependencies
compressor
min. ON time
for compressor(s) in
heat pump
systems.
43.
HP
compressor
min. OFF time
Minimum off time
for compressor(s) in
heat pump
systems.
3 min
0…60 min
44.
Heating min.
ON time
The minimum run
time for the heating
system.
5 min
3…15 min
45.
Heating min.
OFF time
The minimum off
time for the heating
system.
5 min
3…15 min
46.
Cooling min.
ON time
The minimum run
time for the cooling
system
5 min
3…15 min
47.
Cooling min.
OFF time
The minimum off
time for the cooling
system
5 min
3…15 min
48.
Humidifier
(fan) min. ON
time
The minimum run
time for the
humidifier
3 min
0…60 min
The output
must have
been
configured as a
humidifier.
49.
Humidifier
(fan) min. OFF
time
The minimum off
time for the
humidifier
3 min
0…60 min
50.
Dehum. (fan)
min. ON time
The minimum run
time for the
dehumidifier
3 min
0…60 min
The output
must have
been
configured as a
dehumidifier.
51.
Dehum. (fan)
min. OFF time
The minimum off
time for the
dehumidifier
3 min
0…60 min