Commissioning Instructions

Managing application settings
6
22 | 61
A6V11214854_enUS_c
No.
Applicatio
n settings
Descriptions
Factory
settings
Range
Dependencies
33.
Built-in
temp.
sensor adj.
Temperature offset
value for the built-in
room temperature
sensor.
0 K
-5…5 K
Valid only if the
built-in
temperature
sensor is used
to measure the
temperature.
34.
X1 temp.
sensor adj.
Temperature offset
value for the X1
temperature sensor.
0 K
-5…5 K
Valid only if an
external room
temperature
sensor is
connected
using X1.
35.
X2 temp.
sensor adj.
Temperature offset
value for the X2
temperature sensor.
0 K
-5…5 K
Valid only if an
external room
temperature
sensor is
connected
using X2.
No.
Application
settings
Descriptions
Factory
setting
s
Range
Dependencies
36.
Electric
heating coil
fan overrun
Fan will remain
energized for this
amount of time after
heating is de-
energized.
30 s
0…600 s
The thermostat
must be set to
activate fan in
heating mode.
If heat pump,
at least one
stage of aux.
heat must be
enabled.
37.
Damper min.
ON time
Minimum time that
outside air damper
will remain
energized.
3 min
0…60 min
38.
Damper min.
OFF time
The minimum time
between outside air
damper cycles.
3 min
0…60 min
39.
Fan min. ON
time
Minimum run time
for fan when
controlled by
thermostat.
3 min
0…60 min
A fan operation
condition must
be set during
equipment type
selection.
40.
Fan min. OFF
time
Minimum off time
for fan when
controlled by
thermostat.
3 min
0…60 min
41.
Changeover
delay for
heating/coolin
g
The minimum off
time before
switching between
heating and
cooling.
300 s
30…600 s
Heat pump
must be
selected as the
equipment
type.
42.
HP
Minimum run time
3 min
0…60 min
Temperature offsets
Switchover time
adjustment