Commissioning Instructions
Managing application settings
6
A6V11214854_enUS_c
21 | 61
No.
Applicatio
n settings
Descriptions
Factory
settings
Range
Dependenci
es
26.
Comfort air
quality
setpoint
Scheduled air quality
setpoint when space is
occupied. This
setpoint must be lower
than that for
Protection.
900 ppm
0…2000 ppm
Displays only
if the output
is configured
as an outside
air damper in
section
Changing
system setup
[➙ 13].
27.
Economy
air quality
setpoint
Scheduled air quality
setpoint during
transition from
Unoccupied to
Comfort. This setpoint
must be lower than
that for Protection.
1100 pp
m
0…2000 ppm
28.
Unoccupied
air quality
setpoint
Scheduled air quality
setpoint when space is
unoccupied.
1500 pp
m
0…2000 ppm
29.
Protection
air quality
setpoint
The air quality setpoint
if the operating mode
is OFF and
Protection is enabled.
1500 pp
m
0…2000 ppm
No.
Applicatio
n settings
Descriptions
Factory
settings
Range
Dependencies
30.
Humidity
control in
heating
only
Humidification allowed
only when heating
system is energized.
No
N/A
The output
must be
configured as a
humidifier.
31.
Free
cooling
Enables free cooling
by opening the outside
air damper.
No
N/A
The output
must be
configured as
an outside air
damper.
32.
Room
presence
detector
The thermostat
switches from
Unoccupied to
Comfort when
occupancy is
detected.
Active
N/A
N/A
Room air quality
setpoints
Functions