Commissioning Instructions

Managing application settings
6
16 | 61
A6V11214854_enUS_c
No.
Applicatio
n settings
Descriptions
Factory
settings
Range
Dependenci
es
1.
X1 room
temp. ref.
at 0V
Calibrates thermostat
to low end of
temperature sensor
signal (for example,
0 V = 32 )
32 °F
(0 )
-58…176 °F
(-50…80 °C)
A DC 0 to
10 V external
room
temperature
sensor must
be connected
with the
thermostat
using
terminal X1.
2.
X1 room
temp. ref.
at 10V
Calibrates thermostat
to high end of
temperature sensor
signal (for example,
10 V = 122 )
122 °F
(50 )
-58…176 °F
(-50…80 °C)
3.
X2 room
temp. ref.
at 0V
Calibrates thermostat
to low end of
temperature sensor
signal (for example,
0 V = 32 )
32 °F
(0 )
-58…176 °F
(-50…80 °C)
A DC 0 to
10 V external
room
temperature
sensor must
be connected
with the
thermostat
using
terminal X2.
4.
X2 room
temp. ref.
at 10V
Calibrates thermostat
to high end of
temperature sensor
signal (for example,
10 V = 122 )
122 °F
(50 )
-58…176 °F
(-50…80 °C)
5.
Outside
temp. ref.
at 0V
Calibrates thermostat
to low end of
temperature sensor
signal (for example,
0 V = -58 )
-58 °F
(-50 )
-58…176 °F
(-50…80 °C)
A DC 0 to
10 V external
outside air
temperature
sensor must
be
connected.
6.
Outside
temp. ref.
at 10V
Calibrates thermostat
to high end of
temperature sensor
signal (for example,
10 V = 176 )
176 °F
(80 )
-58…176 °F
(-50…80 °C)
Multi-functional inputs