Data Sheet for Product
13
Siemens Industry, Inc.
A6V10807603_enUS_b
Smart Infrastructure
11/23/2021
Operational Data
Setpoint Range
32 to 122 °F (0 to 50 °C)
53.6 to 95 °F (12 to 35 °C) (default)
Built-in Room Temperature Sensor
Temperature range
Accuracy at 77 °F (25 °C)
Display resolution
32 to 122 °F
±0.9 °F or 0.5 °C
1 °F (0.5 °C)
Built-in Room Humidity Sensor
Humidity range
Accuracy at 77 °F (25 °C)
Display resolution
0% to 100%
±5% r.h.
1%
System Compatibility
System Compatibility
Conventional
2 stages cooling, 3 stages heating
Heat pump
2 stages cooling and 2 stages heating (+2
stages auxiliary heating)
Connections
Interfaces
Micro USB
A service port is provided for firmware
upgrade and on-site diagnosis
Wiring Connections
Screw terminals
Solid wires or prepared stranded wires:
Max. 1 x16 to 20 AWG