Data Sheet for Product

12
Siemens Industry, Inc.
A6V10807603_enUS_b
Smart Infrastructure
11/23/2021
Inputs
Connections to Multifunctional Inputs X1 - M - X2
Passive temperature sensors
- Cable length max. (copper
cable
section)
- NTC type
Room temperature range
Outdoor temperature range
- Ni type
Room temperature range
Outdoor temperature range
- Pt type
Room temperature range
Outdoor temperature range
300 ft (90 m) (16 AWG wire), 230 ft (70 m) (18 AWG
wire)
200 ft (60 m) (18 AWG
wire), 130 ft (40 m) (20 AWG
wire)
NTC10K Type 2 Thermistor
32 to 122 °F (0…50 °C)
-32 to 176 °F (-50…80 °C)
Ni1000 at 32 °F (0 °C) RTD
32 to 122 °F (0…50 °C)
-32 to 176 °F (-50…80 °C)
Pt1000_375/Pt1000_385 at 32 °F (0 °C) RTD
32 to 122 °F (0…50 °C)
-32 to 176 °F (-50…80 °C)
Active DC 0 V to 10 V sensors
- Room temperature range
(default)
- Outdoor temperature range
(default)
- Humidity range (default)
- CO
2
range (default)
Note: min./max. configurable via parameters
32 to 122 °F (0…50 °C)
-32 to 176 °F (-50…80 °C)
0 to 100%
0 to 2000 ppm
Digital contacts
- Operating action
- Contact sensing
- Parallel connection
- Input function
Selectable N.O./N.C.
DC 14 to 40 V, 8 mA (typical)
Max. 20 thermostats per switch
Selectable
Outputs
Relay Contact Capacity
Voltage
AC 24 V (±20%)
Current
Min. 0.02 A, Max. 1 A per output