Technical data
Power supply
Power supply
Operating voltage AC 230 V (+10% / -15%)
Frequency 48…63 Hz
Power consumption Max. 9 VA
Standby power consumption (LCD off) 0.6 W
Max. external supply line fusing 10 A circuit breaker
Radio parameters
Radio parameters
Frequency band 2.4…2.4835 GHz
Maximum radio-frequency power 18 dBm
WLAN standard IEEE 802.11b/g/n (HT20)
WLAN channel 1~13
Inputs
Connections to multifunctional inputs X1 - M - X2
Passive temperature sensors
- Cable length max. (copper cable section)
- NTC type
Room temperature range
Outdoor temperature range
- Ni type
Room temperature range
Outdoor temperature range
- Pt type
Room temperature range
Outdoor temperature range
90 m (1.5 mm
2
wire), 70 m (1 mm
2
wire)
60 m (0.75 mm
2
wire), 40 m (0.5 mm
2
wire)
NTC10K at 25 °C
0…50 °C
-50…80 °C
Ni1000 at 0 °C
0…50 °C
-50…80 °C
Pt1000_375/Pt1000_385 at 0 °C
0…50 °C
-50…80 °C
Active DC 0 V ...10 V sensors
- Room temperature range (default)
- Outdoor temperature range (default)
- Humidity range (default)
Min./max. configurable via parameters
0…50 °C
-50…80 °C
0…100%
Digital contacts
- Operating action Selectable NO/NC