current protection device.
● The AC 230 V mains supply line must have an external circuit breaker with a rated cur-
rent of no more than 10 A.
● Properly size the cables to the thermostat and for the outputs for AC 230 V mains volt-
age.
● Use only AC 230 V isolated wired cables, as the conduit box carries AC 230 V mains
voltage.
● Remove wired bridge L - Q11 when loads work with voltages other than AC 230 V.
● Inputs X1-M-X2: Several switches may be connected in parallel. Consider overall max-
imum contact sensing current for switch rating.
● Disconnect from power supply before removing the front of the thermostat.
Commissioning
Refer to the Quick guide and User guide (see Product Documentation) to configure your de-
vice. Commissioning includes the following:
● Internet connection
● Application setup
● Account registration and device pairing
Note:
Before configuring your thermostat, make sure you are connected to the Internet, have a
valid email address, and a smartphone.
Mounting
● The devices are suitable for wall mounting.
● Recommended height: 1.50 m above the floor.
● Do not mount the devices in recesses, shelves, behind curtains or doors, or above or
near heat sources.
● Avoid direct solar radiation.
● Seal the conduit box or the installation tube if any, as air currents can affect sensor read-
ings.
● Adhere to allowed ambient conditions.
Operation
End users can operate the thermostat directly on the touch screen, or download the mobile
app “Siemens Smart Thermostat RDS” and perform operations on their smartphones,
including:
● Creating and managing accounts
● Setting the operating mode (Auto, away, home, manual)