Data Sheet for Product

16
Siemens
A6V10807602_en
--
_h
2021
-
07
-
16
Wiring diagrams
The thermostat is delivered with one wired bridge (L-Q11) for easy installation of
AC 230 V HVAC equipment (example 1).
When loads use voltages other than AC 230 V, bridge must be removed before wiring
the loads to the thermostat (example 2).
If the load current through Y2 is more than 3 A, bridge between L-Q11 cannot be used.
Adapt parameter “Q22/Q24 electrical load” in “Advanced Settings” / “Optimization”.
For application with higher currents (Y1 > 3 A or Y2 > 2 A), adapting parameter
“Q22/Q24 electrical load” in “Advanced Settings” / “Optimization” accordingly is recom-
mended.
Basic
AC 230 V
Advanced
Example 1: Loads =
AC 230 V
Example 2: Loads Y1, Y2
AC 230 V
AC 230 V on Y1, Y2
Y1 HVAC equipment B1, B2 External sensors
Y2 DHW / Dehumidifier / Humidifier S1, S2 External switches
WARNING
The total current rating must not exceed 8 A.